Home » CD3000 S Family » CD3000S 2PH – From 10A to 90A
CD3000S 2PH
Technical Specification
- Voltage power supply: 24V min, 480V Max, 600V on request
- Input Signal: SSR (OFF state <1Vdc ON = 4÷30 Vdc) is standard up to 90A included. Analog input 4÷20mA and 0÷10V is available from 35A (included) to 90A (included)
- Firing: Zero crossing ZC; Burst Firing 4/8/16 with 4÷20mA or 0÷10V with 12÷24V aux. power supply.
- Fan Voltage: 230V ± 15% standard f(110V on request opt., if current ≥75A).
- Heater Break Alarm: Discrimination better than 20%. * Circuit microprocessor based to diagnose partial or total load failure and short circuit on Thyristor. * Latching alarm plus reset. * Relay output 1A at 230V. * Automatic calibration of one or more unit at the same time using a dedicated digital input or using for each unit the calibration button.
- Approvals: Comply with EMC; cULus available as an option on basic units.
- Mounting: Din rail mounting up to 90A included.
- Operating Temperature: 0÷40° up to 90A included (for higher temperature see the derating curve)
Categories: Three Phase (2PH) 2-Leg, CD3000 S Family, Thyristor Power Controller
- General Details
- Code & Size
- Documentation
- Related Products
General Details
CD3000S 2PH
From 10A to 90A
General description
CD3000S 2PH two leg switching three wire load star or delta resistive loads or infrared lamps up to 90A.
- Fully isolated from power.
- Zero crossing firing available with logic input signal (SSR)
- Constant current drain with SSR input
- Analog input 4÷20mA or 0÷10V with burst firing 4, 8 or 16 cycle at 50% power demand, is available as an option from 35A to 90A.
- Heater break alarm (HB) to diagnostic partial or total load failure and short circuit on thyristor, is available as an option from 35A to 90A
- Side by side mounting.
- Special design for heatsink with high dissipation
- Comply with EMC specification CE and cUL
Heater Break Alarm (HB)
- Microprocessor based circuit
- Self learning of current set, via external command or push button on front unit.
- Load break diagnostic with alarm latch.
- Thyristor short circuit diagnostic.
- Alarm reset function and possibility to auto reset the alarm if the normal working condition is restored.
- Alarm output with free voltage contact.
- Available from 35A÷90A incl.
- Full insulation between SSR output coming from controller/multi loop and power supply, no common zero in our unit.
- Easy and fast substitution/calibrate of the unit (also not expert people can do it easy).
Burst Firing (BF)
- This firing performed in digital mode in our unit gives a lot advantage because switch thyristor faster than normal ZC and at the same time without EMC interferences.
- Analog input is necessary for BF and can be decided how many complete cycles we want at 50% of power demand.
- On CD3000S this value can be 4, 8, 16.
- To have a better resolution use REVEX series, where the BF value can be implemented from 1 to
255 complete cycles doing the firing less or more fast.
Documentation
CD3000S 2PH – Documentation
Manuals
Name | Size |
---|
ENG CD3000S-2PH-10-90A USER'S MANUAL CD3000s 2PH from 10 to 90A (M-3000S3-10-90) | 1.1 MiB![]() |
FRA L M CD CD3000S-2PH 10-100A Manuel CD3000S 2PH de 10A à 110A (Version Française) | 0.3 MiB![]() |
FRA L M CD CD3000S-2PH 125-700A Manuel CD3000S 2PH de 125A à 700A (Version Française) | 1.2 MiB![]() |
GER L M CD CD3000S-2PH 35-100A Analog-Input Handbuch CD3000S 2PH Thyristorsteller mit Analogeingang von 35A ÷ 100A | 0.5 MiB![]() |
GER L M CD CD3000S-2PH 10-100A Handbuch CD3000S 2PH Thyristorsteller von 10A ÷ 100A | 0.3 MiB![]() |
ITA L M CD CD3000S-2PH 10-100A Manuale CD3000S 2PH da 10A a 110A | 0.3 MiB![]() |
ITA L M CD CD3000S-2PH 45-100A Analog-Input Manuale CD3000S 2PH da 45A a 100A Ingresso Analogico | 0.4 MiB![]() |
ITA L M CD CD3000S-2PH 45-100A SSR-HB Manuale CD3000S 2PH da 45A a 100A versione Allarme Heater Break | 0.4 MiB![]() |
ITA L M CD CD3000S-2PH 125-700A Manuale CD3000S 2PH da 125A a 700A | 0.8 MiB![]() |
Related Products
CD3000S 1PH – From 10A to 90A
CD3000S 1PH
Technical Specification
- Voltage power supply: 24V min, 480V Max, 600V on request
- Input Signal: SSR , Analog 4÷20mA and 0÷10V is available as an option on units from 15A÷90A included
- Firing: Zero crossing ZC / Burst Firing
- Fan Voltage: Supply 230V ± 15% (110V is available as an option)
- Heater Break Alarm: Discrimination better than 20%. * Circuit microprocessor based to diagnose partial or total load failure and short circuit on Thyristor. * Latching alarm plus reset. * Relay output 1A at 230V. * Automatic calibration of one or more unit at the same time using a dedicated digital input or using for each unit the calibration button.
- Approvals: EMC; cULus available as an option on basic units
- Mounting: Din rail mounting up to 90A included, bulkhead over 110A, IP20 protection
- Operating Temperature: 0÷40° up to 90A included (for higher temperature see the derating curve)
CD3000S 3PH – From 15A to 90A
CD3000S 3PH
Technical Specification
- Voltage power supply: 24V min, 480V Max, 600V on request
- Input Signal: SSR (OFF state <1Vdc ON = 4÷30 Vdc) firing.
- Firing: Zero crossing ZC.
- Auxiliary Voltage Supply: 10Va power consumption.
- Fan Voltage: 230V ± 15%.
- Approvals:Comply with EMC; cULus available as an option.
- Mounting: Din rail mounting up to 90A.
- Operating Temperature: 0÷40° up to 90A included (for higher temperature see the derating curve)